EAR Export Classification: Not subject to the EAR per 15 C.F.R. Chapter 1, Part 734.3(b)(3), except for the following Service Bulletins which are currently published as EAR Export Classification 9E991: SBE70-0992, SBE72-0483, SBE72-0580, SBE72-0588, SBE72-0640, SBE73-0209, SBE80-0024 and SBE80-0025.Copyright
© IAE International Aero Engines AG (2001, 2014 - 2021) The information contained in this document is the property of © IAE International Aero Engines AG and may not be copied or used for any purpose other than that for which it is supplied without the express written authority of © IAE International Aero Engines AG. (This does not preclude use by engine and aircraft operators for normal instructional, maintenance or overhaul purposes.).Applicability
All
Common Information
TASK 24-21-43-700-001 IDG Power Cables - Test The Cables, Testing-001
General
Fig/item numbers in parentheses in the procedure agree with those used in the IPC. Only the primary Fig/item numbers are used. For the service bulletin alpha variants refer to the IPC.
Preliminary Requirements
Pre-Conditions
NONESupport Equipment
| Name | Manufacturer | Part Number / Identification | Quantity | Remark |
|---|---|---|---|---|
| Multimeter | LOCAL | Multimeter | 250 volts DC or equivalent. | |
| Megger Insulation Resistance Tester - BMM80, 250 Volts (200 Gohms) | LOCAL | BMM80 | 250 volts DC or equivalent. |
Consumables, Materials and Expendables
NONESpares
NONESafety Requirements
NONEProcedure
All test equipment used must have a valid National Standards Calibration Certificate.
SUBTASK 24-21-43-820-001 Calibration Procedures for Test Equipment
Set the supply voltage to be 250 volts DC, on the Megger Insulation Resistance Tester - BMM80, 250 Volts (200 Gohms) or equivalent.
Connect the Megger Insulation Resistance Tester - BMM80, 250 Volts (200 Gohms) or equivalent test leads, between the connector body and each pin of the connector.
Make a note of the resistance values.
Pin to Earth - The insulation resistance should be 20 megohms minimum.
If the resistance values are not between the limits, reject the harness. The limits are as follows:
SUBTASK 24-21-43-750-001 Do a Test to Find the Insulation Resistance Value of the IDG Cable Assembly
Set the Multimeter to the continuity setting.
Connect the Multimeter test leads to the contacts at the ends of each wire.
Make sure that the Multimeter shows continuity. If the Multimeter shows no continuity, reject the harness.
SUBTASK 24-21-43-750-002 Do a Test for Continuity of the IDG Cable Assembly